TOP-003-1: Planned Outage Coordination

Purpose
Scheduled generator and transmission outages that may affect the reliability of  interconnected operations must be planned and coordinated among Balancing Authorities, Transmission Operators, and Reliability Coordinators.

Applicability

  • Generator Operators.
  • Transmission Operators.
  • Balancing Authorities.
  • Reliability Coordinators.

Proposed Effective Date
In those jurisdictions where no regulatory approval is required, the standard shall become effective on the latter of either April 1, 2009 or the first day of the first calendar quarter, three months after BOT adoption.  In those jurisdictions where regulatory approval is required, the standard shall become effective on the latter of either April 1, 2009 or the first day of the first calendar quarter, three months after applicable regulatory approval.

Requirements
R1. Generator Operators and Transmission Operators shall provide planned outage information.

R1.1. Each Generator Operator shall provide outage information daily to its Transmission Operator for scheduled generator outages planned for the next day (any foreseen outage of a generator greater than 50 MW).  The Transmission Operator shall establish the outage reporting requirements.

R1.2. Each Transmission Operator shall provide outage information daily to affected Balancing Authorities and Transmission Operators for scheduled generator and bulk transmission outages planned for the next day (any foreseen outage of a transmission line or transformer greater than 100 kV or generator greater than 50 MW) that may collectively cause or contribute to an SOL or IROL violation or a regional operating area limitation.

R1.3. Such information shall be available by 1200 Central Standard Time for the Eastern Interconnection and 1200 Pacific Standard Time for the Western Interconnection.

R2. Each Transmission Operator, Balancing Authority, and Generator Operator shall plan and coordinate scheduled outages of system voltage regulating equipment, such as automatic voltage regulators on generators, supplementary excitation control, synchronous condensers, shunt and series capacitors, reactors, etc., among affected Balancing Authorities and Transmission Operators as required.

R3. Each Transmission Operator, Balancing Authority, and Generator Operator shall plan and  coordinate scheduled outages of telemetering and control equipment and associated  communication channels between the affected areas.

R4. Each Reliability Coordinator shall resolve any scheduling of potential reliability conflicts.

Measures
M1. Evidence that the Generator Operator, Transmission Operator, and Balancing Authority  reported and coordinated scheduled outage information as indicated in the requirements above.