PRC-021-1: Under-Voltage Load Shedding Program Data
Purpose
Ensure data is provided to support the Regional database maintained for Under- Voltage Load Shedding (UVLS) programs that were implemented to mitigate the risk of voltage collapse or voltage instability in the Bulk Electric System (BES).
Applicability
- Transmission Owner that owns a UVLS program.
- Distribution Provider that owns a UVLS program.
Effective Date
August 1, 2006
Requirements
R1. Each Transmission Owner and Distribution Provider that owns a UVLS program to mitigate the risk of voltage collapse or voltage instability in the BES shall annually update its UVLS data to support the Regional UVLS program database. The following data shall be provided to the Regional Reliability Organization for each installed UVLS system:
R1.1. Size and location of customer load, or percent of connected load, to be interrupted.
R1.2. Corresponding voltage set points and overall scheme clearing times.
R1.3. Time delay from initiation to trip signal.
R1.4. Breaker operating times.
R1.5. Any other schemes that are part of or impact the UVLS programs such as related generation protection, islanding schemes, automatic load restoration schemes, UFLS and Special Protection Systems.
R2. Each Transmission Owner and Distribution Provider that owns a UVLS program shall provide its UVLS program data to the Regional Reliability Organization within 30 calendar days of a request.
Measures
M1. Each Transmission Owner and Distribution Provider that owns a UVLS program shall have documentation that its UVLS data was updated annually and includes all items specified in Requirement 1.1 through 1.5.
M2. Each Transmission Owner and Distribution Provider that owns a UVLS program shall have evidence it provided the Regional Reliability Organization with its UVLS program data within 30 calendar days of a request.