Automatic Time Error Correction (IATEC)

Automatic Time Error Correction (IATEC)

The addition of a component , represented by the term IATEC, to the Reporting ACE equation for the Western Interconnection that modifies the control point for the purpose of continuously paying back Primary Inadvertent Interchange and to correct Time Error. Automatic Time Error Correction is only applicable in the Western InterconnectionIATEC shall be zero when operating in any other AGC mode.

The absolute value of IATEC shall not exceed LMax.

IATEC shall be zero when operating in any other AGC mode.

  • Lmax is the maximum value allowed for IATEC set by each BA between 0.2*|Bi| and L10; i.e. 0.2*|Bi|≤ Lmax ≤ L10
  • ε10 is a constant derived from the targeted frequency bound. It is the targeted rootmean-square (RMS) value of ten-minute average Frequency Error based on frequency performance over a given year. The bound, ε 10, is the same for every Balancing Authority Area within an Interconnection.